What’s Vulnerable › Vulnerabilities
CVE-2012-6438: Rockwell Automation ControlLogix PLC Improper Input Validation
- Severity: high (CVSS 7.8 v2.0)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 27.4% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2013-01-24 · updated 2026-06-16
- Weakness: CWE-119
Description
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the NIC to crash. Successful exploitation of this vulnerability could cause loss of availability and a disruption in communications with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400
Affected products
- Rockwell Automation 1756-ENBT: all versions
- Rockwellautomation 1756-Eweb: all versions
- Rockwellautomation 1768-Enbt: all versions
- Rockwellautomation 1768-Eweb: all versions
- Rockwellautomation 1794-Aentr Flex I/O Ethernet/Ip Adapter: all versions
- Rockwellautomation Compactlogix: through 18
- Rockwellautomation Compactlogix Controllers: through 19
- Rockwellautomation Compactlogix L32E Controller: all versions
- Rockwellautomation Compactlogix L35E Controller: all versions
- Rockwellautomation Controllogix: through 18
- Rockwellautomation Controllogix Controllers: through 20
- Rockwellautomation Flexlogix 1788-Enbt Adapter: all versions
- Rockwellautomation Guardlogix: through 18
- Rockwellautomation Guardlogix Controllers: through 20
- Rockwell Automation MicroLogix: through 1100; through 1400
- Rockwellautomation Softlogix: through 18
- Rockwellautomation Softlogix Controllers: through 19
References
- http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102
- https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154
- https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155
- https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156
- https://www.cisa.gov/news-events/ics-advisories/icsa-13-011-03
- http://www.us-cert.gov/control_systems/pdf/ICSA-13-011-03.pdf
Get alerted when CVE-2012-6438 or the next vulnerability affects your stack