What’s Vulnerable › Vulnerabilities
CVE-2018-5459
- Severity: critical (CVSS 9.8 v3.0)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 2.7% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2018-02-13 · updated 2026-06-17
- Weakness: CWE-287
Description
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.
Affected products
- WAGO PFC200: before 02.07.07\(10\) — fixed in 02.07.07\(10\)
How to fix
Upgrade to a fixed version: WAGO PFC200 02.07.07\(10\). Check the vendor advisory for mitigations.
References
- https://ics-cert.us-cert.gov/advisories/ICSA-18-044-01
- https://ics-cert.us-cert.gov/advisories/ICSA-18-044-01
Get alerted when CVE-2018-5459 or the next vulnerability affects your stack