What’s Vulnerable › Vulnerabilities
CVE-2019-10939
- Severity: critical (CVSS 9.8 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 1.1% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2020-04-14 · updated 2026-06-17
- Weakness: CWE-489
Description
A vulnerability has been identified in TIM 3V-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3). The affected versions contain an open debug port that is available under certain specific conditions. The vulnerability is only available if the IP address is configured to 192.168.1.2. If available, the debug port could be exploited by an attacker with network access to the device. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.
Affected products
- Siemens Tim 3V-Ie Advanced Firmware: before 2.8 — fixed in 2.8
- Siemens Tim 3V-Ie Dnp3 Firmware: before 2.8 — fixed in 2.8
- Siemens Tim 3V-Ie Firmware: before 2.8 — fixed in 2.8
- Siemens Tim 4R-Ie Dnp3 Firmware: before 3.3 — fixed in 3.3
- Siemens Tim 4R-Ie Firmware: before 3.3 — fixed in 3.3
How to fix
Upgrade to a fixed version: Siemens Tim 3V-Ie Advanced Firmware 2.8; Siemens Tim 3V-Ie Dnp3 Firmware 2.8; Siemens Tim 3V-Ie Firmware 2.8; Siemens Tim 4R-Ie Dnp3 Firmware 3.3; Siemens Tim 4R-Ie Firmware 3.3. Check the vendor advisory for mitigations.
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-359303.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-359303.pdf
Get alerted when CVE-2019-10939 or the next vulnerability affects your stack