What’s Vulnerable › Vulnerabilities

CVE-2019-13946

Description

Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that include a vulnerable version of the stack. The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device.

Affected products

How to fix

Upgrade to a fixed version: Siemens Ek-Ertec 200 Firmware 4.5; Siemens Ek-Ertec 200P Firmware 4.6; Siemens Profinet Driver 2.1; Siemens Ruggedcom Rm1224 Firmware 4.3; Siemens Scalance M-800 Firmware 4.3; Siemens Scalance S615 Firmware 4.3; Siemens Scalance X-200Irt Firmware 5.3; Siemens Scalance X-400 Firmware 6.0; Siemens Scalance Xb-200 Firmware 3.0; Siemens Scalance Xc-200 Firmware 3.0; Siemens Scalance Xf-200Ba Firmware 3.0; Siemens Scalance Xm-400 Firmware 6.0. Check the vendor advisory for mitigations.

References

Get alerted when CVE-2019-13946 or the next vulnerability affects your stack