What’s Vulnerable › Vulnerabilities
CVE-2019-19279
- Severity: high (CVSS 7.5 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 1.6% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2020-03-10 · updated 2026-06-17
- Weakness: CWE-20
Description
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.
Affected products
- Siemens Siprotec 4: all versions
- Siemens Siprotec Compact: all versions
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf
Get alerted when CVE-2019-19279 or the next vulnerability affects your stack