Description

An attacker could exploit the vulnerability by injecting garbage data or specially crafted data. Depending on the data injected each process might be affected differently. The process could crash or cause communication issues on the affected node, effectively causing a denial-of-service attack. The attacker could tamper with the data transmitted, causing the product to store wrong information or act on wrong data or display wrong information. This issue affects Advant MOD 300 AdvaBuild: from 3.0 through 3.7 SP2. For an attack to be successful, the attacker must have local access to a node in the system and be able to start a specially crafted application that disrupts the communication. An attacker who successfully exploited the vulnerability would be able to manipulate the data in such way as allowing reads and writes to the controllers or cause Windows processes in 800xA for MOD 300 and AdvaBuild to crash.

Affected products

How to fix

Upgrade to a fixed version: ABB AdvaBuild 3.7. Check the vendor advisory for mitigations.

References

Get alerted when CVE-2020-11639 or the next vulnerability affects your stack