What’s Vulnerable › Vulnerabilities
CVE-2020-25178: Rockwell Automation ISaGRAF5 Runtime Cleartext Transmission of Sensitive Information
- Severity: high (CVSS 8.8 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 1.7% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2022-03-18 · updated 2026-06-17
- Weakness: CWE-319
Description
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
Affected products
- Rockwellautomation Aadvance Controller: through 1.40
- Rockwellautomation Isagraf Free Runtime: through 6.6.8
- Rockwell Automation ISaGRAF Runtime: from 5.0 before 6.0 — fixed in 6.0
- Rockwellautomation Micro810 Firmware: all versions
- Rockwellautomation Micro820 Firmware: all versions
- Rockwellautomation Micro830 Firmware: all versions
- Rockwellautomation Micro850 Firmware: all versions
- Rockwellautomation Micro870 Firmware: all versions
- Schneider-Electric Easergy C5 Firmware: before 1.1.0 — fixed in 1.1.0
- Easergy T300 (Firmware version 1.5.2 and older): through 2.7.1
- Schneider-Electric Epas Gtw Firmware: 6.4
- Schneider-Electric Micom C264 Firmware: before d6.1 — fixed in d6.1
- Schneider-Electric Pacis Gtw Firmware: 5.1, 5.2, 6.1, 6.3
- Schneider-Electric Saitel Dp Firmware: through 11.06.21
- Schneider-Electric Saitel Dr Firmware: through 11.06.12
- Schneider-Electric Scd2200 Firmware: through 10024
- Xylem Multismart Firmware: before 3.2.0 — fixed in 3.2.0
How to fix
Upgrade to a fixed version: Rockwell Automation ISaGRAF Runtime 6.0; Schneider-Electric Easergy C5 Firmware 1.1.0; Schneider-Electric Micom C264 Firmware d6.1; Xylem Multismart Firmware 3.2.0. Check the vendor advisory for mitigations.
References
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf
Get alerted when CVE-2020-25178 or the next vulnerability affects your stack