What’s Vulnerable › Vulnerabilities

CVE-2022-1797: Rockwell Automation Logix Controllers Uncontrolled Resource Consumption

Description

A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.

Affected products

How to fix

Upgrade to a fixed version: Rockwellautomation Compact Guardlogix 5370 Firmware 34.011; Rockwellautomation Compact Guardlogix 5380 Firmware 33.011; Rockwellautomation Compactlogix 5370 Firmware 34.011; Rockwellautomation Compactlogix 5380 Firmware 33.011; Rockwellautomation Compactlogix 5480 Firmware 33.011; Rockwellautomation Controllogix 5570 Firmware 34.011; Rockwell Automation ControlLogix® 5580 33.011; Rockwellautomation Guardlogix 5570 Firmware 34.011; Rockwellautomation Guardlogix 5580 Firmware 33.011. Check the vendor advisory for mitigations.

References

Get alerted when CVE-2022-1797 or the next vulnerability affects your stack