What’s Vulnerable › Vulnerabilities
CVE-2022-27640
- Severity: medium (CVSS 6.5 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 0.4% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2022-05-20 · updated 2026-06-17
- Weakness: CWE-400
Description
A vulnerability has been identified in SIMATIC CP 442-1 RNA (All versions < V1.5.18), SIMATIC CP 443-1 RNA (All versions < V1.5.18). The affected devices improperly handles excessive ARP broadcast requests. This could allow an attacker to create a denial of service condition by performing ARP storming attacks, which can cause the device to reboot.
Affected products
- Siemens Simatic Cp 442-1 Rna Firmware: before 1.5.18 — fixed in 1.5.18
- Siemens Simatic Cp 443-1 Rna Firmware: before 1.5.18 — fixed in 1.5.18
How to fix
Upgrade to a fixed version: Siemens Simatic Cp 442-1 Rna Firmware 1.5.18; Siemens Simatic Cp 443-1 Rna Firmware 1.5.18. Check the vendor advisory for mitigations.
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-480937.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-480937.pdf
Get alerted when CVE-2022-27640 or the next vulnerability affects your stack