What’s Vulnerable › Vulnerabilities
CVE-2022-28613: Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series
- Severity: high (CVSS 7.5 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 1.0% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2022-05-02 · updated 2026-06-17
- Weakness: CWE-1284
Description
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
Affected products
- ABB Rtu500 Firmware: from 12.2.1.0 before 12.2.12.0 — fixed in 12.2.12.0
- Hitachi Energy RTU500 series CMU firmware: from 12.0.1.0 before 12.0.14.0; from 12.4.1.0 before 12.4.12.0; from 12.6.1.0 before 12.6.8.0; from 12.7.1.0 before 12.7.4.0; from 13.2.1.0 before 13.2.5.0 — fixed in 12.0.14.0, 12.4.12.0, 12.6.8.0, 12.7.4.0, 13.2.5.0
How to fix
Upgrade to a fixed version: ABB Rtu500 Firmware 12.2.12.0; Hitachi Energy RTU500 series CMU firmware 12.0.14.0, 12.4.12.0, 12.6.8.0, 12.7.4.0. Check the vendor advisory for mitigations.
References
- https://publisher.hitachienergy.com/preview?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launch
- https://search.abb.com/library/Download.aspx?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launch
Get alerted when CVE-2022-28613 or the next vulnerability affects your stack