CVE-2022-30317
- Severity: critical (CVSS 9.1 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 0.9% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2022-08-31 · updated 2026-06-17
- Weakness: CWE-306
Description
Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.
Affected products
- Honeywell Experion Lx Firmware: before r520.1 — fixed in r520.1
How to fix
Upgrade to a fixed version: Honeywell Experion Lx Firmware r520.1. Check the vendor advisory for mitigations.
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-242-07
- https://www.forescout.com/blog/
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-242-07
- https://www.forescout.com/blog/