What’s Vulnerable › Vulnerabilities
CVE-2022-30319
- Severity: high (CVSS 8.1 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 0.7% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2022-07-28 · updated 2026-06-17
- Weakness: CWE-290
Description
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Affected products
- Honeywell Saia PG5 Controls Suite: all versions
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03
- https://www.forescout.com/blog/
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03
- https://www.forescout.com/blog/
Get alerted when CVE-2022-30319 or the next vulnerability affects your stack