What’s Vulnerable › Vulnerabilities
CVE-2022-40179
- Severity: high (CVSS 8.1 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 0.4% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2022-10-11 · updated 2026-06-17
- Weakness: CWE-352
Description
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). A Cross-Site Request Forgery exists in endpoints of the “Operation” web application that interpret and execute Axon language queries, due to the missing validation of anti-CSRF tokens or other origin checks. By convincing a victim to click on a malicious link or visit a specifically crafted webpage while logged-in to the device web application, a remote unauthenticated attacker can execute arbitrary Axon queries against the device.
Affected products
- Siemens Desigo Pxm30-1 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm30.E Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm40-1 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm40.E Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm50-1 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm50.E Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Pxg3.W100-1 Firmware: before 02.20.126.11-37 — fixed in 02.20.126.11-37
- Siemens Pxg3.W100-2 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Pxg3.W200-1 Firmware: before 02.20.126.11-37 — fixed in 02.20.126.11-37
- Siemens Pxg3.W200-2 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
How to fix
Upgrade to a fixed version: Siemens Desigo Pxm30-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm30.E Firmware 02.20.126.11-41; Siemens Desigo Pxm40-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm40.E Firmware 02.20.126.11-41; Siemens Desigo Pxm50-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm50.E Firmware 02.20.126.11-41; Siemens Pxg3.W100-1 Firmware 02.20.126.11-37; Siemens Pxg3.W100-2 Firmware 02.20.126.11-41; Siemens Pxg3.W200-1 Firmware 02.20.126.11-37; Siemens Pxg3.W200-2 Firmware 02.20.126.11-41. Check the vendor advisory for mitigations.
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-360783.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-360783.pdf
Get alerted when CVE-2022-40179 or the next vulnerability affects your stack