What’s Vulnerable › Vulnerabilities

CVE-2022-40182

Description

A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). The device embedded Chromium-based browser is launched as root with the “--no-sandbox” option. Attackers can add arbitrary JavaScript code inside “Operation” graphics and successfully exploit any number of publicly known vulnerabilities against the version of the embedded Chromium-based browser.

Affected products

How to fix

Upgrade to a fixed version: Siemens Desigo Pxm30-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm30.E Firmware 02.20.126.11-41; Siemens Desigo Pxm40-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm40.E Firmware 02.20.126.11-41; Siemens Desigo Pxm50-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm50.E Firmware 02.20.126.11-41; Siemens Pxg3.W100-1 Firmware 02.20.126.11-37; Siemens Pxg3.W100-2 Firmware 02.20.126.11-41; Siemens Pxg3.W200-1 Firmware 02.20.126.11-37; Siemens Pxg3.W200-2 Firmware 02.20.126.11-41. Check the vendor advisory for mitigations.

References

Get alerted when CVE-2022-40182 or the next vulnerability affects your stack