What’s Vulnerable › Vulnerabilities
CVE-2022-40182
- Severity: high (CVSS 8.8 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 1.0% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2022-10-11 · updated 2026-06-17
- Weakness: CWE-250
Description
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). The device embedded Chromium-based browser is launched as root with the “--no-sandbox” option. Attackers can add arbitrary JavaScript code inside “Operation” graphics and successfully exploit any number of publicly known vulnerabilities against the version of the embedded Chromium-based browser.
Affected products
- Siemens Desigo Pxm30-1 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm30.E Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm40-1 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm40.E Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm50-1 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Desigo Pxm50.E Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Pxg3.W100-1 Firmware: before 02.20.126.11-37 — fixed in 02.20.126.11-37
- Siemens Pxg3.W100-2 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
- Siemens Pxg3.W200-1 Firmware: before 02.20.126.11-37 — fixed in 02.20.126.11-37
- Siemens Pxg3.W200-2 Firmware: before 02.20.126.11-41 — fixed in 02.20.126.11-41
How to fix
Upgrade to a fixed version: Siemens Desigo Pxm30-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm30.E Firmware 02.20.126.11-41; Siemens Desigo Pxm40-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm40.E Firmware 02.20.126.11-41; Siemens Desigo Pxm50-1 Firmware 02.20.126.11-41; Siemens Desigo Pxm50.E Firmware 02.20.126.11-41; Siemens Pxg3.W100-1 Firmware 02.20.126.11-37; Siemens Pxg3.W100-2 Firmware 02.20.126.11-41; Siemens Pxg3.W200-1 Firmware 02.20.126.11-37; Siemens Pxg3.W200-2 Firmware 02.20.126.11-41. Check the vendor advisory for mitigations.
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-360783.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-360783.pdf