CVE-2026-3611: Honeywell IQ4x BMS Controller Missing authentication for critical function

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Affected products

How to fix

Upgrade to a fixed version: Honeywell Iq412 Firmware 3.30; Honeywell Iq41X Firmware 3.30; Honeywell Iq422 Firmware 3.30; Honeywell Iq4E Firmware 3.30; Honeywell Iq4Nc Firmware 3.30. Check the vendor advisory for mitigations.