What’s Vulnerable › Vulnerabilities
CVE-2026-3611: Honeywell IQ4x BMS Controller Missing authentication for critical function
- Severity: critical (CVSS 10.0 v3.1)
- Exploited in the wild: not listed in CISA KEV
- EPSS: 5.6% probability of exploitation in the next 30 days
- Public exploit or detection template: none known
- Published: 2026-03-12 · updated 2026-06-17
- Weakness: CWE-306
Description
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Affected products
- Honeywell Iq412 Firmware: before 3.30 — fixed in 3.30
- Honeywell Iq41X Firmware: before 3.30 — fixed in 3.30
- Honeywell Iq422 Firmware: before 3.30 — fixed in 3.30
- Honeywell Iq4E Firmware: before 3.30 — fixed in 3.30
- Honeywell Iq4Nc Firmware: before 3.30 — fixed in 3.30
How to fix
Upgrade to a fixed version: Honeywell Iq412 Firmware 3.30; Honeywell Iq41X Firmware 3.30; Honeywell Iq422 Firmware 3.30; Honeywell Iq4E Firmware 3.30; Honeywell Iq4Nc Firmware 3.30. Check the vendor advisory for mitigations.
References
- https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-069-03.json
- https://www.cisa.gov/news-events/ics-advisories/icsa-26-069-03
- https://www.honeywell.com/us/en/contact